Generator
  • home
  •   > Our Service > Generator
Generator
  • QAC

    ≫ Irresistible benefits :
    1. Stable power delivery of 1MW in a standard 20-foot ISO CSC container for easy, fast and safe installation and transportation.

    2. Low fuel consumption
    The QAC 1250 is equipped with an electric VSD (variable speed) motor-driven cooling fan which ensures optimized fuel consumption (e.g. 10% fuel reduction at full load means a saving of 550 liters per day and 200,000 liter per year).

    3. Better coolant capability
    Due to its intelligent cooling system, the QAC 1250 ensures 100% power at 40°C, at an altitude of 1000 m (a.s.l.). This makes the QAC 1250 ideally suited for use in extreme temperatures and high altitude environments, and lowers the risk for detrimental high temperature shut-downs.

    4. Low noise levels
    With its 67dB(A) at 7 meters, the QAC 1250 is the best choice for sensitive areas.

    5. Standard parallel package
    he QAC 1250 can run alone or in parallel with other equal or different generators either in island mode or PMS(power management system), or in parallel with mains, peak shaving, fixed power and AMF.

    6. Superior standard configuration
    Including the correct protection systems and accessories to run in the extreme and difficult conditions.

    7. Superior service accessibility
    Large acces doors and several service tools make for effortless maintenance, increasing your up-time.

    • QC4002 mk2 controller
      Digital generator management solution.
      - Control possibilities at up to 16 generator parallel   connection
      - Fuel curtailment power management system. Omnipotence   controller module that peak time economy, electric power   transfer and transformer maintenance is convenient
    General
    Dimensions LxWxH (mm) 6060 x 2440 x 2590
    20ft CSC- ISO container
    Mass dry/wet (kg) TBD(<19500)
    Fuel tank capacity (l) 1500
    Sound pressure level LPA (7m) dB (A) 67
    Sound power level LWA dB (A) 98
    Operrating Temperature (°C) ‘-25 ~ 50
    Engine
    50Hz 60Hz
    Engine make Cummins
    Engine model KTA50
    Rated net output (PRP) 1097 1220
    Single step load capability 100% 100%
    Speed governor Electronic
    Alternator
    Alternaator make Leroy Somer
    Rated output 1250kVA 1560kVA
    Insulation (class) H H
    Enclosure protection (IP) 23 23
    Performance data
    50Hz 60Hz
    Rated Active power 3ph 1000kW(1250kVA) 1156kW(1445kVA)
    Rated Current 1804A 1738A
    Performance class
    (acc ISO 8528-5:1993)
    G2
    Single step load acceptance 65% (650kW) 70% (890kW)
    Fuel consumption
    50Hz 60Hz
    0% load 24 liter/hour 34 liter/hour
    50% load 124 liter/hour 147 liter/hour
    75% load 185 liter/hour 214 liter/hour
    100% load 241 liter/hour 276 liter/hour
    Standard option
    · CSC safety approval certification, Gas detector
    · Earth leakage detection, Battery charger
    · PMG excitation system, Coolant heater
    · External fuel tank connection + Auto fuel transfer system
    · Oil level maintainer, Spark arrestor
    · Air inlet shut down valve

    ≫ TECHNICAL DATA
    · Leaflet QAC 1250 [Download]

    · QEC Containarized 800-1250 kVA Mobile Generators [Download]

    · QAS Range Portable Energy English [Download]