Transformer
  • home
  •   > Our Service > Transformer

Installed close to low-voltage devises, a molded transformer is the only means of designing optimized equipment that reduces loss from voltage drop in the electricals.
ABB, whose molded transformer YG-TOMS provides, is the world’s leader in transformer technology that has supplied over 100,000 dry transformers worldwide from its specialized and large-scale production facilities, and owns a wide-range of specialist technology related to molded transformers.

transformer

· Characteristics

- Small area required for installation and reduced total cost.
- Pollution-free and fire-fighting facilities not required.
- Convenient maintenance and insulating oil not required.
- Eco-friendly and safe / flame retardant and no risk of fire.
- High short-circuit strength and excellent overload capacity.

· Technical Specifications

※ Customized production available.

transformer
≫ 690V
General specification Frequency [Hz] 50 / 60
Rated capacity [kVA] 600
High tension (Rated voltage) [V] 690
Low pressure (Rated voltage) [V] 400 / 415 / 440
Special quality Efficiency (100% load factor, 1 PE) [%] 98.7
% impedance [%] 5 ± 10% IEC tolerance
Impulse withstand voltage BIL, (high tension/low pressure) [kV] - / -
Power frequency withstand voltage, (high tension/low pressure) [kV] 3 / 3
Noise (LpA) measurement : 1.0m dB (A) 62
Size : transformer/enclosure (when apply) Width (± 5% tolerance) [mm] 1530 / 2000
Deeply, (± 5% common difference)[mm] 800 / 1400
High, (± 5% common difference)[mm] 1430 / 1900
Weight (± 5% tolerance) [kg] 2000 / 550

≫ 6600-11000V
General specification Frequency [Hz] 50 / 60
Rated capacity (Janaeng/windchill) [kVA] 3150
High tension (Rated voltage) [V] 11000-6600
Low pressure (Rated voltage) [V] 380 / 400 / 415 / 440
Special quality Efficiency (100% load factor, 1 PE) [%] 99.1
% impedance (At 11 kVs) [%] 6.0 ± 10% IEC tolerance
No-load current [%] 1.0 ± 30% IEC tolerance
Voltage regulation (100% load factor, 1 PE) [%] 1.0
Impulse withstand voltage BIL, (high tension/low pressure) [kV] 75 / -
Power frequency withstand voltage, (high tension/low pressure) [kV] 28 / 3
Noise (LpA) measurement : 1.0m dB (A) 70